dc.description.abstract |
State estimation has been adopted by the power system researchers in the late 1960’s.
Later on, state estimation was applied to the transmission system. Recently state
estimation has become cornerstone among the modern control centers tools for the
automation of distribution system. In this research work, state estimation has been
implemented for automatic feeder reconfiguration. Automatic feeder reconfiguration can
be accomplished by matching the impedances of two different feeders. Once the
impedances are matched, static transfer switch perform the feeder reconfiguration
effectively and efficiently.
The liability of power distribution companies is to provide reliable and good quality
power to the customers. Due to the technological advancement and the large scale
production, usage of the sensitive equipment has been increased. The sensitive equipment
requires quality power through reliable power delivery system. Power delivery system
includes feeders and laterals to transfer power from the substation to the consumer end.
As the feeders and the laterals are radially operated, therefore the chances of power
interruption always exist. Power interruption may occur either due to faults or due to the
maintenance or replacement of any components of the distribution system e.g. a
distribution transformer. Voltage sag is another cause of interruption of sensitive
equipment. To overcome this problem, sensitive equipment should be fed through two
independent feeders. If the preferred feeder fails, the sensitive load should be transferred
to the alternate feeder. A fast and efficient transfer switch can complete this transfer.
Static transfer switch (STS) system has been developed to transfer the load from the
preferred feeder to the alternate feeder when voltage sag or fault occurs on the preferred
feeder. The most important parameter of the STS-system is the speed of operation or the
transfer time so that the load should not be interrupted. To reduce the transfer time and
hence to expedite the transfer process, it is necessary that both feeders have the same
voltage angle at the point-of-installation (PoI) of the STS. If the impedances of both the
feeders are identical then voltage phase difference will be zero. To match the impedance,
state estimator has been designed to estimate the voltage angle of both the feeders. To
mitigate the voltage phase difference, shunt capacitor has been installed and consequently
the transfer time of the STS has been reduced.
However, the control logic strategy of the STS-system also affect the transfer time. Two
different control logic techniques namely delay logic and forced commutation technique,
have been developed and simulated using PSCAD/EMTDC software. If the delay logic
technique is utilized then the voltage phase angle of both feeders must be identical. The
developed state estimation technique can be implemented to match the impedances and
hence the voltage angle to reduce the STS transfer time. However, forced commutation
technique can accommodate the phase difference by commutating the outgoing thyristor
forcefully. But forced commutation technique require more components e.g. capacitor,
inductor, auxiliary thyristors etc. Both techniques are implemented to solve the problems
related to the feeder overloading.
The problem of overloading has been solved through feeder reconfiguration. STS-system
installed at critical location, transfer the sensitive load to the lightly loaded alternate
feeder. This phenomenon can be termed as feeder reconfiguration using load-balancing.
The development of the STS-system has solved the problem of load interruption. The
reliability of the power distribution system has been improved and the sensitive load now
operates without power interruption. |